North Hyde substation fire review (Heathrow outage)
Date
2025; government response November 2025
Issued by
National Energy System Operator (NESO)
CompletedEvidence: Primary text read
4
Facts
1
Deadlines
2
Sources
Summary
One substation fire on 20 March 2025 cut power to 71,655 customers and closed Heathrow. The review found a fault reading from 2018 not acted on and an airport switch-over that took 10–12 hours and had never been exercised. Its 12 recommendations were accepted.
Key facts
- A moisture reading found in July 2018 was not acted on as its severity required.[1]
- The fire cut power to 71,655 customers; Hillingdon Hospital, roads and rail were affected, and three data centres switched to backup generators.[1]
- Heathrow needed 10–12 hours to reconfigure its internal network and had not exercised that scenario; more than 270,000 passenger journeys were disrupted.[1]
- Twelve recommendations across nine themes, including continuity guidelines for energy-dependent sectors and cross-sector dependency mapping, were accepted in November 2025.[1][2]
Requirements and what happened
| Requirement | Deadline | What happened | Verdict |
|---|---|---|---|
| Implement the 12 recommendations[2] | From November 2025 | Accepted; implementation under way. | Not yet due |
Analysis (BioR's interpretation)
- The UK mapped critical sectors but not the dependencies between them; the grid did not know which customers were critical.